Hi all,
please help with understanding on something that I have been working lately;
ventilation ducting design.
Engine Room - about 150 m3 volume.
On the starboard there are 2 Inlet ducts; supported with fans - duct A=0,5 m2
On the portside there are 2 Outlet ducts; without fans - duct A=0,3 m2 (smaller than Air-in duct)
Required E.R. airflow 40 m3/h EDIT: 40000 (11 m3/s); resulting 5,5 m3/s for duct (two ducts)
Air in per fan, flow rate: 8 m/s
Grilles: 6 m/s
Each air OUT duct must exhaust around 6 m3/s - how can I easily check this?
E.R. temp: 40 C
Out temp: 30 C
Temp difference: 10 C
My concerns are:
How can I calculate whether this volume/cross section "A" of exhaust duct air will be able to escape the engine room fast enough and hence result in excessive back pressure in ER through the duct of above mentioned "A"?
How can I calculate ER pressure; and maintain positive/negative pressure in ER? Does it need to be positive pressure in ER?
How can I calculate that the estimated back pressure of the air out system is high enough to prevent the engine room ventilation system from delivering the flow rate required to maintain the Delta-T value at <=10⁰C, when vessel machinery is operating at 100%?
P.S. Preferring not to use fans in Air-out ducting, maybe re-designing duct area...
Thank you in advance.
please help with understanding on something that I have been working lately;
ventilation ducting design.
Engine Room - about 150 m3 volume.
On the starboard there are 2 Inlet ducts; supported with fans - duct A=0,5 m2
On the portside there are 2 Outlet ducts; without fans - duct A=0,3 m2 (smaller than Air-in duct)
Required E.R. airflow 40 m3/h EDIT: 40000 (11 m3/s); resulting 5,5 m3/s for duct (two ducts)
Air in per fan, flow rate: 8 m/s
Grilles: 6 m/s
Each air OUT duct must exhaust around 6 m3/s - how can I easily check this?
E.R. temp: 40 C
Out temp: 30 C
Temp difference: 10 C
My concerns are:
How can I calculate whether this volume/cross section "A" of exhaust duct air will be able to escape the engine room fast enough and hence result in excessive back pressure in ER through the duct of above mentioned "A"?
How can I calculate ER pressure; and maintain positive/negative pressure in ER? Does it need to be positive pressure in ER?
How can I calculate that the estimated back pressure of the air out system is high enough to prevent the engine room ventilation system from delivering the flow rate required to maintain the Delta-T value at <=10⁰C, when vessel machinery is operating at 100%?
P.S. Preferring not to use fans in Air-out ducting, maybe re-designing duct area...
Thank you in advance.