Hi Amp Interupt Capacity Circuit Breakers

Discussion in 'OnBoard Electronics & Controls' started by Willallison, Nov 20, 2011.

  1. michael pierzga
    Joined: Dec 2008
    Posts: 4,862
    Likes: 116, Points: 0, Legacy Rep: 1180
    Location: spain

    michael pierzga Senior Member

    Sure...Ive got a 24v 1500 amp battery bank. What is an automatic battery cell monitoring system ...how does it work...heat sensors ?
     
  2. jehardiman
    Joined: Aug 2004
    Posts: 3,773
    Likes: 1,167, Points: 113, Legacy Rep: 2040
    Location: Port Orchard, Washington, USA

    jehardiman Senior Member

    Different cell types and system requirements have different sensors but generaly temp, electrolyte level, s.g., present voltage, present amp draw, % charge, Ah left, H2 levels, are all things that are monitored. There is a fairly wide variety of systems out there from those for computer backup lithium cells to electric car systems, to 1MW submarine wet cell stacks (which is where the copper bus bar and an axe comment comes from). Just google "automatic battery cell monitoring system"
     
  3. cyclops2
    Joined: Sep 2010
    Posts: 242
    Likes: 8, Points: 0, Legacy Rep: 94
    Location: New Jersy

    cyclops2 Senior Member

    Well

    A QP 20 or 30 amp household circuit breaker, ranges from 5,000 to 10,000 interrupting amps. Home Despot & Lowes
     
  4. DCockey
    Joined: Oct 2009
    Posts: 5,229
    Likes: 634, Points: 113, Legacy Rep: 1485
    Location: Midcoast Maine

    DCockey Senior Member

    That may be an Alternating Current only rating. Battery banks on boats are Direct Current. Interupt ratings are frequently higher for AC than for DC because with AC the current goes to zero twice every cycle.
     
  5. cyclops2
    Joined: Sep 2010
    Posts: 242
    Likes: 8, Points: 0, Legacy Rep: 94
    Location: New Jersy

    cyclops2 Senior Member

    Does this help ?

    Grainger.com sells the Schneider Electric Company line of DC circuit breakers that are rated for 10,000 amps DC interrupting capacity, with adjustable high & low trip points.
     
  6. cyclops2
    Joined: Sep 2010
    Posts: 242
    Likes: 8, Points: 0, Legacy Rep: 94
    Location: New Jersy

    cyclops2 Senior Member

    Square D had their QO breakers rated in both AC & DC.

    To be fail safe with DC batteries.
    ALWAYS put in a fuse. They never have a bad day.
    When you are unsure. ALWAYS put in a fuse.
     

  7. Willallison
    Joined: Oct 2001
    Posts: 3,590
    Likes: 130, Points: 0, Legacy Rep: 2369
    Location: Australia

    Willallison Senior Member

    Thanks all... will look into it further.....
    Personally, I couldn't see the problem with a T fuse.... but I was asked the question and I hadn't looked into such larger interrupt capacity breakers before....
     