Maybe I do not understand you all right....
Correct
Ok..what engines do you have in the ER..and do you have any generators too?
To install this app on your iPhone:
Note: This feature may not be available in some browsers.
Maybe I do not understand you all right....
The grill is to be horizontally orientated.Following my technical book a rectangular duct 0.7 m * 0.45 m has the same pressure loss as an round pipe of a diameter of 0.55 m (cross section areas are not the same, but the friction is). If the walls of the duct (leghth 2 m) are fair, there will be a pressure loss of 16 Pa = 16 N/m² . (A coarse surface would signifantly increase the pressure loss.) The grill resistance is to add. Is the grill horizontally oriented (rain in the ER)? If it is vertically oriented, the change of the direction of the airstream causes an additional resistance.
Correct
Ok..what engines do you have in the ER..and do you have any generators too?
At least something I said is correct.
So, there are two diesel generators. each 65 kW.
Scania Diesel Gen OL 621 C / HCM 534 C - 265 kWNeed make model number and tech data to get the spec's....since this give the heat rejection etc.
[...]
My dilemma is not the required air for ER, my dilemma is whether the Outlet duct 0,3m2 x 2 PSC (0,6m2 SUM) are enough to exhaust around 6 m3/s of air?
Saying that the velocity in each duct must be 10 m/s to satisfy this requirement (there are two ducts of 0,3m2).
How can I check what air velocity will be in the duct without fan in Outlet duct (natural non-forced air out)..?
[...]
but 20 m/s is a lot and pressure loss increases with air velocity.
Required E.R. airflow 40 m3/h ....
Well, according to those engine specs: https://www.scania.com/content/dam/...s/pdf/specs/power-gen/DC16_43A_500-550kVA.pdf
I get that you need roughly around 6.2m^3/sec or 370 m3/min
So...in order to ascertain if the numbers you have posted are correct - which could be the source of your dilemma in trying to calculate required air flow etc - what size and type of engines are in your ER..and what other, if any, sources of combustion too..such as gensets etc.
So, there are two diesel generators. each 65 kW
40000 m3/h (around 11 m3/s), is the result I have for required ER airflow, since there are other equipment in the ER, not only generators....
...to make it less confusional,...